Description
PHILIPS Explosion Proof Tri-proof EX686C LED56 NW PSR L600 911401905482
Tri-proof 40 W luminaire for Zone 2 gas and Zone 21/22 dust areas: 5,600 lm at 4000K, 120° optics, IP66 and IK08, dimmable driver.
91140190548240 W4000K120°IP66 / IK08Ex ec IIC T6...T4 Gc
Ordering data of the EX686C LED56
The 12NC is the ordering key. Prices, stock and the LM79 file for this code are on request.
Installing this code
- Mounting. Stainless clips on a flat surface, 1 m pre-wired cable. The 1246 mm body needs fixings at both ends; no separate accessory is required.
- Cable entry. One NPT 3/4 threaded entry; use a certified Ex-rated gland or blanking plug. An uncertified gland voids the declared marking.
- Circuit. 100-277 V AC, 50/60 Hz, Class I. Surge protection of 10 kV line to earth is built into the driver compartment, so no external SPD is needed at the fitting.
- Dimming. 1-10V as standard. Keep the dimming pair separate from the mains run.
Accessories: No accessory is required: clips and 1 m cable are included with the batten.
Specifications
| Light output | |
| Rated power | 40 W |
| Luminous flux | 5,600 lm |
| Efficacy | 140 lm/W |
| Beam angle | 120° |
| Colour temperature | 4000K (neutral white) |
| Colour rendering | Ra ≥ 80, SDCM ≤ 6, blue light RG1 |
| UGR | 32 |
| Electrical | |
| Supply | 100-277 V AC, 50/60 Hz |
| Power factor | ≥ 0.95 |
| THD | ≤ 20% at 220 V AC |
| Dimming | 1-10V |
| Flicker | Flicker-free, PstLM ≤ 1, SVM ≤ 0.4, MD ≤ 3.2% |
| Surge protection | 10 kV line to earth |
| Insulation class | Class I, over-temperature protection in the driver |
| Mechanical | |
| Dimensions | 653 × 106 × 125 mm |
| Weight | 3.10 kg |
| Housing | Polycarbonate |
| Finish | Powder coating, RAL 7040 |
| Mounting | Ceiling surface |
| Cable entry | NPT 3/4 |
| Sealing and impact | IP66 / IK08, 500 hours salt mist |
| Protection and compliance | |
| Gas marking | II 3G Ex ec IIC T6...T4 Gc, Zone 2 |
| Dust marking | II 2D Ex tb IIIC T85°C...T105°C Db, Zone 21 and 22 |
| Lifetime | 50,000 hours L70 at 35 °C |
| Warranty | 5 years |
| Certification | CCC, GB3836 and IEC60079 reports, LM79, EMC, RoHS and REACH |
Values at 35 °C ambient, tolerance per IEC 62717. IES, LDT and ULD files on request.
The four bodies of the EX68X range
The gallery below is shared across the series: the first image is the Tri-proof body used by this code.
All 46 codes in the series
The current code is highlighted. Every other description opens the data sheet of that code.
| 12NC | Description | Power / CCT / Flux |
|---|---|---|
| EX689W Explosion proof floodlight — 50–450 W, 7,000–63,000 lm, yoke bracket. 20 codes. | ||
| 911401905440 | EX689W LED70/CW PSR | 50W / 6500K / 7,000 lm |
| 911401905441 | EX689W LED140/CW PSR | 100W / 6500K / 14,000 lm |
| 911401905442 | EX689W LED168/CW PSR | 120W / 6500K / 16,800 lm |
| 911401905443 | EX689W LED210/CW PSR | 150W / 6500K / 21,000 lm |
| 911401905444 | EX689W LED280/CW PSR MB | 200W / 6500K / 28,000 lm |
| 911401905445 | EX689W LED350/CW PSR MB | 250W / 6500K / 35,000 lm |
| 911401905446 | EX689W LED420/CW PSR NB | 300W / 6500K / 42,000 lm |
| 911401905447 | EX689W LED490/CW PSR NB | 350W / 6500K / 49,000 lm |
| 911401905448 | EX689W LED560/CW PSR NB | 400W / 6500K / 56,000 lm |
| 911401905449 | EX689W LED630/CW PSR NB | 450W / 6500K / 63,000 lm |
| 911401905450 | EX689W LED70/NW PSR | 50W / 4000K / 7,000 lm |
| 911401905451 | EX689W LED140/NW PSR | 100W / 4000K / 14,000 lm |
| 911401905452 | EX689W LED168/NW PSR | 120W / 4000K / 16,800 lm |
| 911401905453 | EX689W LED210/NW PSR | 150W / 4000K / 21,000 lm |
| 911401905454 | EX689W LED280/NW PSR MB | 200W / 4000K / 28,000 lm |
| 911401905455 | EX689W LED350/NW PSR MB | 250W / 4000K / 35,000 lm |
| 911401905456 | EX689W LED420/NW PSR NB | 300W / 4000K / 42,000 lm |
| 911401905457 | EX689W LED490/NW PSR NB | 350W / 4000K / 49,000 lm |
| 911401905458 | EX689W LED560/NW PSR NB | 400W / 4000K / 56,000 lm |
| 911401905459 | EX689W LED630/NW PSR NB | 450W / 4000K / 63,000 lm |
| EX688P Explosion proof high bay — 40–200 W, 5,600–28,000 lm, ceiling or side bracket. 10 codes. | ||
| 911401905460 | EX688P LED56/CW PSR | 40W / 6500K / 5,600 lm |
| 911401905461 | EX688P LED98/CW PSR | 70W / 6500K / 9,800 lm |
| 911401905462 | EX688P LED140/CW PSR MB | 100W / 6500K / 14,000 lm |
| 911401905463 | EX688P LED210/CW PSR MB | 150W / 6500K / 21,000 lm |
| 911401905464 | EX688P LED280/CW PSR MB | 200W / 6500K / 28,000 lm |
| 911401905465 | EX688P LED56/NW PSR | 40W / 4000K / 5,600 lm |
| 911401905466 | EX688P LED98/NW PSR | 70W / 4000K / 9,800 lm |
| 911401905467 | EX688P LED140/NW PSR MB | 100W / 4000K / 14,000 lm |
| 911401905468 | EX688P LED210/NW PSR MB | 150W / 4000K / 21,000 lm |
| 911401905469 | EX688P LED280/NW PSR MB | 200W / 4000K / 28,000 lm |
| EX687P Explosion proof platform light — 30 and 60 W, 3,900 / 7,800 lm, wire guard. 4 codes. | ||
| 911401905470 | EX687P LED39/CW PSR | 30W / 6500K / 3,900 lm |
| 911401905471 | EX687P LED78/CW PSR | 60W / 6500K / 7,800 lm |
| 911401905472 | EX687P LED39/NW PSR | 30W / 4000K / 3,900 lm |
| 911401905473 | EX687P LED78/NW PSR | 60W / 4000K / 7,800 lm |
| EX686C Explosion proof tri-proof batten — 20–80 W, 2,800–11,200 lm, 600 and 1200 mm. 12 codes. | ||
| 911401905474 | EX686C LED28/CW PSR L600 | 20W / 6500K / 2,800 lm |
| 911401905475 | EX686C LED42/CW PSR L600 | 30W / 6500K / 4,200 lm |
| 911401905476 | EX686C LED56/CW PSR L600 | 40W / 6500K / 5,600 lm |
| 911401905477 | EX686C LED56/CW PSR L1200 | 40W / 6500K / 5,600 lm |
| 911401905478 | EX686C LED84/CW PSR L1200 | 60W / 6500K / 8,400 lm |
| 911401905479 | EX686C LED112/CW PSR L1200 | 80W / 6500K / 11,200 lm |
| 911401905480 | EX686C LED28/NW PSR L600 | 20W / 4000K / 2,800 lm |
| 911401905481 | EX686C LED42/NW PSR L600 | 30W / 4000K / 4,200 lm |
| 911401905482 | EX686C LED56/NW PSR L600 | 40W / 4000K / 5,600 lm |
| 911401905483 | EX686C LED56/NW PSR L1200 | 40W / 4000K / 5,600 lm |
| 911401905484 | EX686C LED84/NW PSR L1200 | 60W / 4000K / 8,400 lm |
| 911401905485 | EX686C LED112/NW PSR L1200 | 80W / 4000K / 11,200 lm |
Accessories are quoted with the luminaires and have no separate page.
Other PHILIPS ranges for the same plant
Frequently asked questions
Which hazardous areas is the EX686C LED56/NW PSR L600 rated for?
The EX686C LED56/NW PSR L600 carries the dual marking: II 3G Ex ec IIC T6...T4 Gc for Zone 2 gas, and II 2D Ex tb IIIC T85 °C...T105 °C Db for Zone 21 and Zone 22 dust. It is not rated for Zone 0, Zone 1 or Zone 20, and the zone drawing of the plant governs the installation.
What output and optics does the EX686C LED56 deliver?
It delivers 5,600 lm at 40 W from a 120° optic at 4000K, with Ra ≥ 80 and SDCM ≤ 6. The body measures 653 × 106 × 125 mm and weighs 3.10 kg.
How is the EX686C LED56/NW PSR L600 supplied, dimmed and protected?
It runs on 100-277 V AC, 50/60 Hz, power factor at or above 0.95, insulation Class I. Dimming is 1-10V. Surge protection is 10 kV line to earth and the driver is over-temperature protected. Sealing is IP66 with IK08 impact resistance and 500 hours salt mist.